Switching

RMG 4S (base module) 4-Channel Switching Actuator

The MIX series is a series of devices, consisting of base modules (e.g. RMG 4 S or RMG 4 C load) and extension modules (e.g. RME 4 S or RME 4 C load). To one basis module of this series, up to 2 extension modules of this series can be connected.

Every channel of these switching actuators has
an LED for displaying what state the switch is in and a hand switch with the On/Off/bus positions. The switching actuators can adopt a parameterized state within 1 second after the return of mains power and are therefore suited for use in units in accordance with VDE 0108.
The properties of the basic functions of switching, delay switching and pulse function can be set by means of parameters.

The following can also be parameterised: no. per channel links, contact type (contact breaker/
contact maker) along with the activation upon central commands such as steady-On, steady-Off, central switching and storing/calling scene.

  • Switching power 16 A, extendable to 12 channels
  • Feedback object for each channel
  • Central objects with and without priority
  • Switching functions: On/Off, pulse, On/Off-delay, stairway light with pre-warning in accordance with DIN 18015-2
  • Logical operations: Disable, AND, Enable, OR Calling and storing scenes
  • Adjustable reaction to bus failure
  • Adjustable reaction to the return of bus or mains activity
  • Hand switch with On, Off, bus, switching also without bus voltage

« Back to product section

Specification

Supply voltage provided by the current net
Operating voltage 230 VAC ± 10%, 50 Hz
Power consumption 2.5 VA
Supply voltage provided by the KNX net (base module only)
Power consumption Max. 10 mA (incl. 2 upgrades)
Connection Bus terminal
Output number 4 closing contacts
Type of contact Floating
Rated voltage 230 V AC, 50 to 60 Hz
Rated current 16 A/250 V AC, cos j = 1. 10 A/250 V AC, cos j = 0.6
Switching of different phases Possible
Switching SELV Possible if all 4 channels of a SELV module can switch
Switching capacity:
Ohmic load 3.680 W
Capacitive load Max.42 µF
Incandescent lamp load 2.300 W
HV halogen lamp load 2.300 W
Fluorescent lights:
Uncompensated 26 × 40 W, 20 × 58 W,
10 × 100 W
Parallel compensated 10 × 40 W (4.7 µF),
20 × 58 W (7.0 µF), 2 × 100 W (18 µF)
Dual switch (KVG): 10 x (2 × 58 W),
5 x (2 × 100 W)