Product Categories
Timeguard, proud to be a part of the Theben group.
BSI Registered. Certificate No. Q05884
Heating
FCA 1 Fan Coil Actuator
FCA 1 is a fan coil actuator suitable for operation
on the KNX.
FCA 1 controls the fan coil with up to 3 fan stages. It also controls the heating and cooling valve, whereby 2-way and 3-way valves can be actuated. An additional relay allows the selective control of an electric heater bank or an electric cooler bank. 2-pipe systems and 4-pipe systems are supported.
FCA 1 has 2 free-floating inputs for window contacts and monitoring humidity. The window contact input can be reconfigured as a temperature sensor.
- The operating state is displayed via 9 LEDs:
- 3 LEDs (red) for displaying the fan stage
- 1 red LED for displaying heating mode
- 1 blue LED for displaying cooling mode
- 1 red LED for displaying additional relay ON
- 2 red LEDs for displaying input 1 and/or input 2 closed
- 1 red LED for displaying manual mode
- FCA1 has 2 keys for easier set-up. One key selects various fan stages
The other key enables toggling between heating and cooling modes.
Specification
| Supply voltage provided by the current net operating voltage | 230 V, ± 10%, 50 Hz |
|---|---|
| Power draw from the mains | Max. 3 VA |
| Bus power supply: Bus power draw | Max. 10 mA |
| Bus connection | Bus terminal |
| Outputs: Valves (triacs switching capacity) | 0.5 A (24–230 V AC) |
| Switching capacity, additional relay | 16 A |
| Switching capacity, ventilator relay | 8 A |
| Response in the event of bus failure | adjustable |
| Permissible ambient temperature | –5 °C … +45 °C |
| Protection class | II provided it is correctly installed |
| Protection rating | IP 20 in accordance with EN 60529 |
| Standard housing | 45 × 72 × 60 mm (4 modules), installation on DIN top hat rail |
NOTE: Timeguard has a policy of continuous product development and reserve the right to alter specifications at any time. Therefore, unavoidable differences between product and website specifications may occur, for which liability cannot be accepted by Timeguard.